8615167740056

load break switch (LBS) ,Indoor load break switch (LBS)FKN12-12 Indoor load break switch (LBS) 12KV

FKN12-12 Indoor load break switch (LBS) 12KV

FKN12-12D Series air- blast load break switch and FKRN12A- 12D series air- blast load break switch-fuse combination apparatus are new series switchgear applies to three- phase electric distribution system of rated 12KV, acting as protecting and control apparatus for transformers, cable and overhead wiring. These series are especially applicable in rural. urban terminal substation and prefabricated substations, as well as ring network power supply.

     FKRN12-12 Series with fuse switch,it can break and make over-current, load current and short-circuit current(limited current fuse).

This product is featured with impact structure, aesthetic appearance reliable interlock and high insulating level. In the spring storage operating mechanism. ON/OFF speed is free from the influence of the manpower. For the arc-extinguish electric arc-extinguish inside the insulating cover. the free gas occurs at sparking do not cause descend of insulating level between phases and phase to earth. The insulating cover clapboard separates electrified part thus boost protection grade of ring main unit. The copper-tungsten contact and main contact brings along reliable conductivity and long life. This product achieves sound fame due to easy maintenance and operations as well as reliable performance. It is in compliance with per IEC62271-105.

 

 

 

 

 

Environment condition

  1. The altitude: under 1000M.
  2. The ambient temperature: -25℃-+40℃.
  3. The relative humidity of air: monthly≤90%, daily≤95%.
  4. Amplitude: Earthquake degree 8.
  5. Application occasions should free from fire, inflammables, explosives, corrosives and severe vibration.
Request a Quote

PRODUCTS DETAILS

FKN12-12 Indoor load break switch (LBS) 12KV

FKN12-12D Series air- blast load break switch and FKRN12A- 12D series air- blast load break switch-fuse combination apparatus are new series switchgear applies to three- phase electric distribution system of rated 12KV, acting as protecting and control apparatus for transformers, cable and overhead wiring. These series are especially applicable in rural. urban terminal substation and prefabricated substations, as well as ring network power supply.

     FKRN12-12 Series with fuse switch,it can break and make over-current, load current and short-circuit current(limited current fuse).

This product is featured with impact structure, aesthetic appearance reliable interlock and high insulating level. In the spring storage operating mechanism. ON/OFF speed is free from the influence of the manpower. For the arc-extinguish electric arc-extinguish inside the insulating cover. the free gas occurs at sparking do not cause descend of insulating level between phases and phase to earth. The insulating cover clapboard separates electrified part thus boost protection grade of ring main unit. The copper-tungsten contact and main contact brings along reliable conductivity and long life. This product achieves sound fame due to easy maintenance and operations as well as reliable performance. It is in compliance with per IEC62271-105.

 

 

 

 

 

Environment condition

  1. The altitude: under 1000M.
  2. The ambient temperature: -25℃-+40℃.
  3. The relative humidity of air: monthly≤90%, daily≤95%.
  4. Amplitude: Earthquake degree 8.
  5. Application occasions should free from fire, inflammables, explosives, corrosives and severe vibration.

No.

Item

Unit

Parameter

FN12-12D/630-20

FN12-12D.R/100-31.5

1

Rated voltage

kV

12

2

Rated frequency

Hz

50

3

Rated current

A

630

100

4

Lighting impulse resisting voltage

kV

75/85

5

1min power frequency with stand voltage

kV

42/48

6

Rated heat - stability current

kA

20(4S)

7

Rated machine-stability current

kA

50

8

Rated closing current (peak)

kA

50

 

9

Rated short-circuit breaking current

kA

 

31.5

10

Rated transfer current

kA

 

1.5

11

Max. breaking current

kA

1.8

12

Breaking no-load transformer capacity

KVA

1250

13

Rated cable charging current

A

10

14

Rated power load current breaking times

time

>100

15

Switch-off time of rated power load current switch on-and-off

S

 

>0.06

16

Earth switch heat-stability current

kA

20(2S)

20(2S)

17

Earth switch heat-stability current (peak)

kA

50

50

18

Motor operating power voltage

V

AC220,DC48

N5.jpg

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

Return