8615167740056

load break switch (LBS) ,Indoor load break switch (LBS) FN5-12 Indoor load break switch (LBS) 12KV

FN5-12 Indoor load break switch (LBS) 12KV

FN5-12 model indoor AC HV load break switch-fuse combination apparatus is developed and designed based on international technology and national power supply requirement, it passed all type tests and trial-operation inspections.

The apparatus conforms to IEC420: AC load break switch and fuse combination apparatus.

Compared to international product it keeps up with technical level with small volume and light weight. It is applicable in ring main unit and prefabricated substations as well as 12kv line and power distribution system.

The product realizes three working positions: power making. power breaking and earth. It applies to power system of rated voltage 6- 12kv, 50/60HZ breaking load current over load current and short-circuit current.

Environment condition

  1. The altitude: under 1000M.
  2. The ambient temperature: -25℃-+40℃.
  3. The relative humidity of air: monthly≤90%, daily≤95%.
  4. Amplitude: Earthquake degree 8.
  5. Application occasions should free from fire, inflammables, explosives, corrosives and severe vibration.
Request a Quote

PRODUCTS DETAILS

The product realizes three working positions: power making. power breaking and earth. It applies to power system of rated voltage 6- 12kv, 50/60HZ breaking load current over load current and short-circuit current.

Environment condition

  1. The altitude: under 1000M.
  2. The ambient temperature: -25℃-+40℃.
  3. The relative humidity of air: monthly≤90%, daily≤95%.
  4. Amplitude: Earthquake degree 8.
  5. Application occasions should free from fire, inflammables, explosives, corrosives and severe vibration.

 

 

 

Technical parameter

NO

Item

Units

Technical parameters

1

Rated voltage

kV

10

2

Maximum working voltage

kV

12

3

Rated current

A

200

400

630

4

Rated short-time withstand current(4s)

kA

6

12.5

20

5

Rated peak withstand current

kA

15

31.5

50

6

Rated closed loop breaking current

A

200

400

630

7

Rated loading breaking current

A

200

400

630

8

Rated loading breaking current (5%)

A

10

20

31.5

9

Rated short circuit closing current

kA

15

31.5

50

10

Power frequency withstand voltage

kV

42(Fracture:48)

 Lightning impulse withstand voltage

75(Fracture:84)

11

Open/close operating torque

 N.m(N)

90(180)

100(200)

             

 

 

 

 

 

 

 

 

 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

Return