FZN25-12 Indoor load break switch (LBS) 12KV

FZN25-12D/T630-20 Type Indoor AC high voltage load switch is three-phase AC 50Hz, rated voltage of 12kV and indoor installations, for industrial and mining enterprises for distribution in clinics and substations and other occasions, as electrical protection and control facilities for the division and load current, loop current, no load transformer and cable charging current.

       As the combination of electrical transformers and other electrical equipment on the protective effect than the circuit more reliable, more economical, especially for rings, double radiation power supply units and box-type substation.

Request a Quote

PRODUCTS DETAILS

 Product overall structure in the form of operator arrangement in the primary loop on the side.(according to user requirements to provide the primary loop right and left side or the form of positive).Leading electrical part by insulation cover, static contact, coils, vacuum arcing chamber, such as flow fuse combination also electrical appliances co., LTD., with short circuit protection function.

 Environment condition

  1. The altitude: under 1000M.
  2. The ambient temperature: -25℃-+40℃.
  3. The relative humidity of air: monthly≤90%, daily≤95%.
  4. Amplitude: Earthquake degree 8.
  5. Application occasions should free from fire, inflammables, explosives, corrosives and severe vibration.

 

 

 

 

Technical parameter

No.

Item

Unit

Value

1

Rated voltage

kV

12

2

Rated frequency

Hz

50

3

Rated current

A

630

4

Rated insulation level

1min power frequency withstand voltage

kV

Arc-quenching chamber fracture 30

Effective value

Earth ,phase 42, insulating fracture 48

Lightning impulse withstand voltage (peak)

Earth ,phase 75, insulating fracture 85

5

Rated dynamic current (peak)

kA

50

 

6

4S thermal current

kA

20

 

7

Rated power load breaking current

A

630

 

8

Rated closed-loop breaking current

A

630

 

9

Rated cable charge breaking current

A

10

 

10

Rated breaking no-load transformer capacity

kV

1250

11

Rated transfer current

A

2000

12

Fuse model

 

XRNT-12

13

Striker output energy

J

2~5

14

Rated short-circuit closed current

kA

50

80(predictive value)

15

Earth switch rated dynamic current

kA

50

16

Earth switch 2s thermal current

kA

20

17

Auxiliary circuit rated voltage

V

~220  ~110

18

Mechanical life

times

10000

19

Opening time of fuse trigger

ms

30~40

20

Opening time of tripper trigger

ms

40~50