8615167740056

Vacuum Circuit Breaker(VCB)12KV 24KV 36KV BKV3-12KV vacuum circuit breaker

BKV3(VS1)-12KV vacuum circuit breaker

in terms of mechanisms,VS1-Series vacuum circuit breakers are given special optimization to transmission parts. Modular spring mechanisms have such advantages as convenient maintenance, short power-off maintenance, high versatility of parts, and boast better compatibility with vacuum interrupters which greatly improves the technical parameters.

Request a Quote

PRODUCTS DETAILS

Product Description

BKV3-12KV vacuum circuit breaker

Product Description

BKV3(VS1)-12KV vacuum circuit breaker

BKV3-12 indoor H.V. vacuum circuit breaker is an indoor switchgear with three-phase, rated voltage of 12kV, control and protection for industrial and mining enterprises, power plants and substations, electrical facilities, and for frequent operation place adopting VET operating mechanism and circuit breaker integrated design can be used as a fixed installation unit can also be equipped with special advance mechanism, the composition of handcart unit used some of the main circuit can use the whole solid seal post with high reliability, maintenance-free, in order to achieve smaller circuit breakers, can be equipped with KYN28A 12 and other handcart switch cabinet. In the home it can also be used with fixed XGN switchgear.

VS1-Series circuit breaker features high stability and high reliability

In terms of mechanisms, VS1-Series vacuum circuit breakers are given special optimization to transmission parts. Modular spring mechanisms have such advantages as convenient maintenance, short power-off maintenance, high versatility of parts, and boast better compatibility with vacuum interrupters which greatly improves the technical parameters and delivers more excellent performance.

Applicable standards

1EC62271-100 High-voltage switchgear and control-gear-Part 100: Alternating-current circuit-breakers

Secondary circuit

VS1-Series vacuum circuit breakers adopt modular design for their secondary control circuit boards. The electric connection of the mechanisms employs high-grade self-fastener plugs, which both facilitates replacement and ensures reliable electrical connection * High-performance oil buffer

High-performance oil buffer

High-performance breaking buffer can markedly reduce the overshoot and rebounding amplitudes of the moving contact of a vacuum circuit breaker in breaking thus avoiding the loss of mechanical endurance due to partial over fatigue of vacuum interrupter bellows resulting from moving contact overshoot. As the rebounding amplitudes of the moving contact reduces, No re-ignition and restrike is found during the switching capacitor bank test

 

Item

Unit

20kA

25kA

31.5kA

40kA

Rated Voltage

kV

10

Max working voltage

kV

12

Rated Current

A

630

1250

1250

 1600

 2500

 3150

1250

 1600

 2500

 3150

Rated short circuit breaking current

kA

20

25

31.5

40

Rated short circuit making current (peak)

kA

50

63

80

100

Rated peak withstand current

kA

50

63

80

100

4s rated short time withstand current

kA

20

25

31.5

40

Rated insulation

 level

Power frequency withstand voltage

kV

42(fracture48)

Impulse withstand voltage

75(fracture85)

Rated sequence of operation

 

0-0.3s-CO-180s-CO

Mechanical life

time

10000

Breaking times of rated short circuit breaking current

time

50

Operating voltage

V

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

Return