8615167740056

Vacuum Circuit Breaker(VCB)12KV 24KV 36KV ZW20-12 Outdoor vacuum circuit breaker

ZW20-12 model outdoor AC vacuum circuit breaker
used to make and break load current, overload current and short-circuit current in 12kV, 50/60Hz power system. It's applicable for substations, industry and mining, urban and rural electricity power networks, especially applicable in occasions with frequent operation and automatic power distribution network.
Request a Quote

PRODUCTS DETAILS

Product Description

ZW20-12 Outdoor vacuum circuit breaker

Product Description

ZW20-12 model outdoor AC vacuum circuit breaker is used to make and break load current, overload current and short-circuit current in 12kV, 50/60Hz power system. It's applicable for substations, industry and mining, urban and rural electricity power networks, especially applicable in occasions with frequent operation and automatic power distribution network. It accords with the standards of IEC62271-100 &GB1984 AC high voltage circuit breaker, GB/T 11022 HV General technical requirement of switches and control apparatus.

Product feature

1. Ideal apparatus in urban and rural electricity network reform : Remote function:remote control, remote metering, remote communication and remote adjustment.

2. Flexible operating: Both power storage and CO operation are motor and manual operated, remote and local operation are both available.

3. Excellent breaking capability: Break short-circuit current 25kA up to 30 times.

4. Small operation power and high dependability: The small motor-driving spring operation mechanism with new design is of lowest operation power (about 30W).

5. Multiple installations: Pole mounted and pad mounted.

6. Reliable sealing: The mature sealing technology assures reliable sealing performance

7. Particular incoming and outgoing method: Silicon rubber bushing to make enough insulate distance.

8. Safe operation: Anti-explosive device mounted on the top of box prevents heated gas and maters from spattering out when inner fault occurs.

Ambient condition

1. Altitude: ≤ 2000m

2. Ambient temperature: -40°C~+40°C

3.The wind speed does not exceed 34m / s (equivalent to 700pa on the cylindrical surface)

4. Maximum Temperature Drop: no more than 25°C

5. There will be have dew under the condition of high temperature low down hastily.

Technical parameter

Name

Unit

Data

Rated   voltage

 KV

 12

Rated   power frequency

 Hz

50 

Rated   current

 KA

 630/1000

Rated   short-circuit breaking current

KA 

 20/25

Rated   withstand current(peak)

KA 

 50/63

Rated   short-time withstand current(4s)

KA 

 20/25

Rated   short-circuit making current(peak)

KA 

 50/63

Mechanical   life

 Secondary

 10000

Rated   short-circuit breaking time

 Secondary

 30

Power frequency withstand voltage

(1min) :( wet) (dry) white, right\fracture

 KV

 42/48

Lighting impulse withstand voltage

(peak) and white, right \ fracture

 KV

 75/85

Secondary circuit 1min power

frequency withstand voltage

KV

 2

Weight

kg

180

SF6 rated gage pressure

Mpa

0

 

 

 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

Return