8615167740056

Vacuum Circuit Breaker(VCB)12KV 24KV 36KV ZW32-40.5 outdoor vacuum circuit breaker

ZW32-40.5 type outdoor vacuum circuit breaker

Service condition

1. ambient air temperature: + 40°C ~ -40 °C

2. a height of not more than 2000 meters above sea level

3. the wind speed is not greater than 35m/s

4. anti-contamination level for grade IV

5. the earthquake intensity does not exceed 8 degrees

6. no fire, explosion, severe chemical corrosion of the place

Request a Quote

PRODUCTS DETAILS

Product Description

ZW32-40.5 outdoor vacuum circuit breakerProduct Description

ZW32-40.5 type outdoor vacuum circuit breaker is rated voltage 35kV, three-phase AC 50Hz outdoor distribution equipment. Mainly used for breaking, closing power system load current, overload current and short circuit current For substation and industrial and mining enterprises distribution system protection and control of workplace use, and frequent operation of rural power grids. The circuit breaker vacuum interrupter technique using solid seal, external insulation silicon rubber sleeve, long life and high reliability, actuator can be miniaturize, highly reliable spring mechanism may also be advanced permanent magnet body. You can also configure isolating switches and intelligent controllers, with but when slicer kind of coincidence used, enabling four remote functions and distribution automation.

Service condition

1. ambient air temperature: + 40°C ~ -40 °C

2. a height of not more than 2000 meters above sea level

3. the wind speed is not greater than 35m/s

4. anti-contamination level for grade IV

5. the earthquake intensity does not exceed 8 degrees

6. no fire, explosion, severe chemical corrosion of the place

Product technical parameter

Item

Unit

Data

Rated voltage

 KV

35

Rated current

 KA

630/1250/1600

Rated frequency

HZ

50/60

Power frequency withstand voltage 1min(wet)(dry)

KV

80 95/95

Lightning impulse with stand voltage(peak)

KV

185

Rated short circuit breaking current

KA

20/25/31.5

Rated short circuit switching current(peak)

KA

63/80

Rated peak with stand current

KA

63/80

4s short time with stand current

KA

25/31.5

Rated short circuit breaking times

times

30

Mechanical life

times

10000

Control voltage of mechanism

V

AC/DC220

Secondary circuit 1min power frequency voltage

KV

2

clearance between open contacts

mm

16±1

Contact over-travelling distance

mm

4±0.5

Opening speed

m/s

1.4-1.8

Closing speed

m/s

0.4-0.8

Contact closing bounce time

ms

≤5

Distance of phase to phase

mm

560±2

The circuit resistance of each phase

Ω

<120

Closing time

ms

25-45

Opening time

ms

20-45

weight

KG

295

 

 

 

Contact us

Please feel free to give your inquiry in the form below We will reply you in 24 hours

Leave YourMessage

Thank you! We will reply you via email within 24 hours.

Return