8615167740056

VS1-24 indoor fixed circuit breaker 24kv(insulated cylinder)

VS1-Series circuit breaker features high stability and high reliability

In terms of mechanisms, VS1-Series vacuum circuit breakers are given special optimization to transmission parts. Modular spring mechanisms have such advantages as convenient maintenance, short power-off maintenance, high versatility of parts, and boast better compatibility with vacuum interrupters which greatly improves the technical parameters and delivers more excellent performance.

Request a Quote

PRODUCTS DETAILS

Applicable standards

1EC62271-100 High-voltage switchgear and control-gear-Part 100: Alternating-current circuit-breakers

Secondary circuit

VS1-Series vacuum circuit breakers adopt modular design for their secondary control circuit boards. The electric connection of the mechanisms employs high-grade self-fastener plugs, which both facilitates replacement and ensures reliable electrical connection.

 

 

 

 

 

 

 

 

 

Technical parameter:

Item

Unit

20kA

25kA

31.5kA

40kA

Rated Voltage

kV

20

Max working voltage

kV

24

Rated Current

A

630

1250

1600
2500

1600
2500

Rated short circuit breaking current

kA

20

25

31.5

40

Rated short circuit making current (peak)

kA

50

63

80

100

Rated peak withstand current

kA

50

63

80

100

4s rated short time withstand current

kA

20

25

31.5

40

Rated insulation
level

Power frequency withstand voltage

kV

42(fracture48)

Impulse withstand voltage

75(fracture85)

Rated sequence of operation

 

0-0.3s-CO-180s-CO

Mechanical life

time

10000

Breaking times of rated short circuit breaking current

time

50

Operating voltage

V

AC/DC110, 220

Moving contactor travel

mm

11±1

Contactor over travel

mm

4±0.5

Three-phase opening/closing asynchronous

ms

≤2

Contact closing bounce time

ms

≤2

Average opening speed

m/s

0.9~1.2

Average closing speed

m/s

0.4~0.8

Opening time

Under max operation voltage

s

≤0.05

Under min operation voltage

≤0.08

Closing time

s

≤0.1

Each phase main loop resistance

µΩ

≤40

Allowable attrition thickness of moving and fixed contact

mm

3

 